Back to Top

1
Hi, Guest!
  • Durag
  • Durag AAL 76 Flame Monitor

Durag AAL 76 Flame Monitor

Update Terakhir
:
12 / 11 / 2021
Min. Pembelian
:
1 Unit

Harga

CALL
PT. Surrama Tridaya Mandiri adalah perusahaan yang bergerak dalam bidang usaha importir , distributor alat-alat instrument : flowmeter, gas detector, control valve, safety valve, pressure reducing valve, dll

Detail Durag AAL 76 Flame Monitor

Durag AAL 76 Flame Monitor
Fire water monitor

Particularly cost-effective, fail-safe flame monitors for the monitoring of gas and oil burners as well as gas and oil fired igniters.

Overview

  • Monitoring of gas and oil burners as well as gas and oil fired igniters of any load
  • Ionisation flame monitoring for continuous operation and intermittent operation
  • Simple installation on 35 mm rails according to IEC/EN 60715
  • Confirmed by TÜV SÜD for applications up to SIL 2

Technical Data

AAL 76 P0D/... for continuous operation and intermittent operation
AAL 76 P0I/... for intermittent operation
Operating voltage 230 V or special voltages: 115 V / 125 V / 250 V
Ambient temperature - 30 °C to + 60 °C
Flame Monitor Safety time (flame failure detection time ffdt) ≤ 1/3/5 s
Display LED
Protection category: Housing IP 40
Protection category: Plug-in terminal blocks IP 20
Flame signal output 90 - 110 VDC
Housing attachement on 35 mm DIN-rail
Dimensions 68 x 104 x 119 mm (WxHxD)
Weight approx. 0.55 kg
Tampilkan Lebih Banyak