Operational mode | Intermittent operation or continuous operation |
Safety | Self-monitoring and fail-safe, supports safesupports safety chains up to SIL3 |
Auxiliary supply | 24 VDC, 7W, PELV |
Flame relay | 1x NO contact, 250 VAC, 2 A 1x NC contact, 250 VAC, 2 A |
Status relay | 1x NO contact, 250 VAC, 2 A |
Flame Failure Detection Time (FFDT) | 0.5 ... 5 s (adjustable in steps of 0.5 s) |
Analogue output | 0/4...20 mA, 750 Ohm max. |
Spectral ranges | UV, VIS, IR |
Number of ranges | 1 |
Threshold switch | Flame intensity |
Viewing angle | 6° (with fibre optic System) |
Communication | LEDs, always visible at a glance for all versions |
Perm. ambient temperature | -40...+75°C |
Protection class | IP66/IP68, NEMA 4X IP65, NEMA 4X (/MP7) |
Dimensions | 100 x 100 mm, length approx. 180 mm (housing M5) |
Weight (w/o cable) | approx. 1.3 kg (housing M5) |