Operation mode | Intermittent operation, continuous operation, 72-hour operation without continual supervision |
Safety | Self-monitoring and fail-safe |
Power supply | 24 VDC, 115/230 VAC |
Protection | IP00 |
Flame relay | 1x switch-over contact, 230 VAC, 2 A |
Status relay | 1x switch-over contact, 230 VAC, 2 A |
Threshold setting | 00...99 |
Safety time | 1 ... 5.5 s |
Pre-configurable combinations of switching threshold and safety time | 3 |
Flame sensor connection | 1 or 2 (parallel) |
Display | alpha-numeric LCD display |
Flame intensity | 0/4...20 mA |
Flame signal | 0/4...20 mA |
Perm. ambient temperature | -20...+60°C |
Dimensions | 19” plug-in module, 3 RU, 21 HP |
Weight | approx. 1 kg |